R
4 Installation Guide for Dimming and Switching Panels
Panel Model Number Guide (continued)
Prefix
CCP = Custom combination panel
Module Types
_X _L _A _M _F _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
L = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM
Ballast Control (TVM)
Feed Voltage
120 for 120 V
GRAFIK SystemsTM (CCP) (120 V only)
Example
CCP-2X2L 1A4T-1204ML-20-CGP___
Module Quantity Limits
Panel Size Feed type TVM 4A 4U 4M
Mini Feed-through NA Any combination up to 3 modules
Mini Feed-through 0-4 Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Mini Breakers NA Any combination up to 3 modules
Mini Breakers 0-4 Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
Standard Feed-through NA Any combination up to 9 modules
Standard Feed-through 0-12 Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Standard Breakers (main lugs) NA Any combination up to 9 modules
Standard Breakers (main lugs) NA Any combination up to 7 modules
Standard Breakers (main lugs) 0-12 Any combination up to 8 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
Standard Breakers (main lugs) 0-12 Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Notes
Consult Lutron for panels with custom breaker needs.
TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
TVM = NA is not TVM-ready
XP
0
0
0
0
Modules:
Quantity and Type
Prefix Feed
Voltage
Feed
Type
Custom
Panel Suffix
(contact Lutron for custom options)
Branch
Circuit
Breaker
Rating
Feed T
ype / Input Ratings
FT = feed-through panel (circuit breakers not included) /
120 V
3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4ML = 3 phase 4 wire feed / 120/208 V
2 = 1 phase 2 wire input breakers (mini only)
3 = 1 phase 3 wire input breakers (mini only)
4 = 3 phase 4 wire input breakers (mini only)
Branch Circuit Breaker Rating
20 = 20 A branch circuit breakers
15 = 15 A branch circuit breakers
Custom Panel Suf
fix (optional)
Indicates panel with special options
Frequency
(All Model Numbers and Voltages): 50/60 Hz
Output (Load) Ratings
Module T
ype Rating
XP, 4U 16 A per circuit
4A 16 A per module, 10 A per output
4M 16 A per module, 5 A per output
(1/4 HP motor)
4FSQ 2 A per output (single ceiling fan)
TVM 50 mA per channel, 750 mA per system